BARRERA DE SEGURIDAD INTRINSECA, ALIM 24 VDC, ENT NAMUR/CONTACTO, SAL RELÉ

Cod.: KFD2-SR2-Ex2.W

 

Switch Amplifier KFD2-SR2-Ex2.W

  • 2-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Dry contact or NAMUR inputs
  • Relay contact output
  • Line fault detection (LFD)
  • Reversible mode of operation
  • Up to SIL2 acc. to IEC 61508
  • FUENTE: http://www.pepperl-fuchs.com/global/en/classid_6.htm?view=productdetails&prodid=26055


Datasheet excerpt: Technical data of KFD2-SR2-Ex2.W

General specificationsSupplyInputOutputTransfer characteristicsDirective conformityConformityAmbient conditionsMechanical specificationsData for application in connection with Ex-areasInternational approvals

 

Esp. Técntica: Alt. Disponible [ Descargar ]


 

Puedes agregar este producto a tu lista de cotizacion:

UND

PEPPERL FUCHS
Signal typeDigital Input
ConnectionPower Rail or terminals 14+, 15-
Rated voltage20 ... 30 V DC
Ripple≤ 10 %
Rated current≤ 50 mA
Power loss1 W
Power consumption< 1.3 W
Connectionterminals 1+, 2+, 3-; 4+, 5+, 6-
Rated valuesacc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit currentapprox. 8 V DC / approx. 8 mA
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detectionbreakage I ≤ 0.1 mA , short-circuit I > 6 mA
Pulse/Pause ratiomin. 20 ms / min. 20 ms
Connectionoutput I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12
Output I, IIsignal, relay
Contact loading253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
Minimum switch current2 mA / 24 V DC
Energized/De-energized delayapprox. 20 ms / approx. 20 ms
Mechanical life107 switching cycles
Switching frequency≤ 10 Hz
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Low voltage
Directive 2006/95/ECEN 61010-1:2010
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Degree of protectionIP20
Massapprox. 150 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) , housing type B2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
EC-Type Examination CertificatePTB 00 ATEX 2080 , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protectionEx-HexagonII (1)G [Ex ia Ga] IIC 
Ex-HexagonII (1)D [Ex ia Da] IIIC 
Ex-HexagonI (M1) [Ex ia Ma] I
Error message output
Maximum safe voltage Um40 V DC (Attention! Um is no rated voltage.)
Statement of conformityPF 08 CERT 0803
Group, category, type of protectionEx-HexagonII (3)G [Ex ic Gc] IIC
Statement of conformityTÜV 99 ATEX 1493 X , observe statement of conformity
Group, category, type of protection, temperature classEx-HexagonII 3G Ex nA nC IIC T4
Directive conformity
Directive 94/9/ECEN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010
FM approval