General specifications
Signal type | Digital Input |
Supply
Connection | Power Rail or terminals 14+, 15- |
Rated voltage | 20 ... 30 V DC |
Ripple | ≤ 10 % |
Rated current | ≤ 50 mA |
Power loss | 1 W |
Power consumption | < 1.3 W |
Input
Connection | terminals 1+, 2+, 3-; 4+, 5+, 6- |
Rated values | acc. to EN 60947-5-6 (NAMUR) |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
Line fault detection | breakage I ≤ 0.1 mA , short-circuit I > 6 mA |
Pulse/Pause ratio | min. 20 ms / min. 20 ms |
Output
Connection | output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12 |
Output I, II | signal, relay |
Contact loading | 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load |
Minimum switch current | 2 mA / 24 V DC |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms |
Mechanical life | 107 switching cycles |
Transfer characteristics
Switching frequency | ≤ 10 Hz |
Directive conformity
Electromagnetic compatibility | |
| Directive 2004/108/EC | EN 61326-1:2006 |
Low voltage | |
| Directive 2006/95/EC | EN 61010-1:2010 |
Conformity
Electromagnetic compatibility | NE 21:2006 |
Degree of protection | IEC 60529:2001 |
Ambient conditions
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications
Degree of protection | IP20 |
Mass | approx. 150 g |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) , housing type B2 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with Ex-areas
EC-Type Examination Certificate | PTB 00 ATEX 2080 , for additional certificates see www.pepperl-fuchs.com |
| Group, category, type of protection | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
Error message output | |
| Maximum safe voltage Um | 40 V DC (Attention! Um is no rated voltage.) |
Statement of conformity | PF 08 CERT 0803 |
| Group, category, type of protection | II (3)G [Ex ic Gc] IIC |
Statement of conformity | TÜV 99 ATEX 1493 X , observe statement of conformity |
| Group, category, type of protection, temperature class | II 3G Ex nA nC IIC T4 |
Directive conformity | |
| Directive 94/9/EC | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 |
International approvals
FM approval | |
Esp. Técntica: Alt. Disponible [ Descargar ]
Puedes agregar este producto a tu lista de cotizacion: